설비 전기히터 용량별 전류,전선,차단기 전정섭 2011. 1. 4. 21:59 히타 용량암페어(A)차단기선정(A)내열선 선정(mm2)단자 저항값[Ω]kw1Ø3Ø1Ø3Ø1Ø3Ø1Ø3Ø 220V220V380V220V220V380V220V220V380V220V220V380V1 4.55 2.62 1.52 202020222 48.40 96.80 288.8 2 9.09 5.25 3.04 202020222 24.20 48.40 144.4 3 13.64 7.87 4.56 202020222 16.13 32.27 96.27 4 18.18 10.50 6.08 3020203.522 12.10 24.20 72.20 5 22.73 13.12 7.60 3030203.522 9.68 19.36 57.76 6 27.27 15.74 9.12 4030205.53.52 8.07 16.13 48.13 7 31.82 18.37 10.63 4030205.53.52 6.91 13.83 41.26 8 36.36 20.99 12.15 5040205.53.52 6.05 12.10 36.10 9 40.91 23.62 13.67 60403083.53.5 5.38 10.76 32.09 10 45.45 26.24 15.19 60403085.53.5 4.84 9.68 28.88 11 28.87 16.71 4030 5.53.5 4.40 8.80 26.25 12 31.49 18.23 5030 5.53.5 4.03 8.07 24.07 13 34.11 19.75 5030 5.53.5 3.72 7.45 22.22 14 36.74 21.27 5040 5.53.5 3.46 6.91 20.63 15 39.36 22.79 5040 5.53.5 3.23 6.45 19.25 16 41.99 24.31 7540 85.5 3.03 6.05 18.05 17 44.61 25.83 7540 85.5 2.85 5.69 16.99 18 47.23 27.35 7550 85.5 2.69 5.38 16.04 19 49.86 28.87 7550 85.5 2.55 5.09 15.20 20 52.48 30.38 7550 85.5 2.42 4.84 14.44 21 55.11 31.90 7550 85.5 2.30 4.61 13.75 22 57.73 33.42 10050 85.5 2.20 4.40 13.13 23 60.35 34.94 10050 5.5 2.10 4.21 12.56 24 62.98 36.46 10075 5.5 2.02 4.03 12.03 25 65.60 37.98 10075 8 1.94 3.87 11.55 26 68.23 39.50 10075 8 1.86 3.72 11.11 27 70.85 41.02 10075 8 1.79 3.59 10.70 28 73.47 42.54 12575 8 1.73 3.46 10.31 29 76.10 44.06 12575 8 1.67 3.34 9.96 30 78.72 45.58 12575 8 1.61 3.23 9.63 31 81.35 47.10 12575 1.56 3.12 9.32 32 83.97 48.61 12575 1.51 3.03 9.03 33 86.60 50.13 12575 1.47 2.93 8.75 34 89.22 51.65 12575 1.42 2.85 8.49 35 91.84 53.17 12575 1.38 2.77 8.25 36 94.47 54.69 125100 1.34 2.69 8.02 37 97.09 56.21 125100 1.31 2.62 7.81 38 99.72 57.73 125100 1.27 2.55 7.60 39 102.3 59.25 150100 1.24 2.48 7.41 40 105.0 60.77 150100 1.21 2.42 7.22 전선의 안전 전류표전선의종류중 우리는 600볼트CV 또는6 00볼트EV(전력케이블 전선)4가닥(1c는접지)전선종류/㎜2 ㎜ 3.5 5.5 814223860100 암페아/A 23 33 44 5476100140190260